Phase sequence: you do not need a special instrumentDo you need a special instrument?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Guidance Note 3 · p.93. Phase sequencing is done at each point of the installation, to confirm every conductor is in the right place.
| Method | How |
|---|---|
| By inspection | Brown lands where brown belongs, through the busbar, at every point |
| By continuity | With the circuit isolated, test between two line conductors as you would an R1 + R2, then the next pair, then the last |
| With an AVI | The rotation test — below |
The probe sequence
The two probe tips are labelled L1 and L2. 1. L1 probe → L1 L2 probe → L2 2. L1 probe → L2 L2 probe → L3 3. L1 probe → L3 L2 probe → L1 You want the R arrow lighting up on all three.
✋The AVI rotation check is a live test. You are working on a live three-phase board. Treat it accordingly. Only the continuity method is done dead.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing