Exactly as they are on the site.
Line and neutral pins joined with a clip, the other lead on the metal you can touch. 500 V DC.
- Switch the equipment on first, with all its covers in place. A switch left off leaves part of the live conductors out of the test.
- Shredder: >999 MΩ, class II minimum 2 MΩ. Hot plate: >999 MΩ, class I minimum 1 MΩ. Record the greater-than sign.
- Polarity: on a moulded plug, a multifunction tester can’t prove it — you can’t see inside. Record N/C, not checked — the key on Form 4.1. On a lead, polarity is checked by continuity, pin to matching contact (10.10(d), p.75): a dedicated PAT tester does it with its cord test.
Then functional: plug it in, it works, it switches off. Suitable for where it’s used? Suitable for continued use? Initials, and a pass sticker.
Code of Practice · 10.6 · Table 10.2 · minimum insulation resistance
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing