PAT earth continuity, worked out properly0.08 ohms on a hot plate. Pass?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: 0.08 ohms on a hot plate. Pass? The answer is in the notes below.
The notes
Exactly as they are on the site.
Hot plate. Null the leads. Clamp one tight on the plug’s earth pin and put the other on the metalwork itself — an exposed-conductive-part, not the earth terminal screw. The book is specific: on the screw, you’ve only proved the connection to the screw. Flex the cable while you watch; a reading that jumps or climbs is a poor connection. Say it reads 0.08 Ω.
The limit
Maximum = 0.1 Ω + R of the flex R = (mΩ/m × length) ÷ 1000 = (26 × 1) ÷ 1000 = 0.026 Ω (0.75 mm², 1 m) Maximum = 0.1 + 0.026 = 0.126 Ω Measured 0.08 Ω ≥ 0.026, ≤ 0.126 ✓
Code of Practice · 10.5.2 · Table 10.1
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing