Nulling your leadsWhy null every single time?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: Why null every single time? The answer is in the notes below.
The notes
Exactly as they are on the site.
This is the one step that quietly ruins readings. With crocodile clips on the ends, set to continuity, press test and the meter shows 0.2 Ω — that is the leads alone. Press the null button, test again, and it reads zero with null shown on the display.
Nulling, in order
1. Clips on, fixed jaw to fixed jaw — not moving jaw to moving jaw. The fixed jaws grip harder and give a better reading. 2. Set the dial to continuity. 3. Press test -> reads the resistance of the leads (about 0.2 Ω). 4. Press null, press test again -> reads zero, display says null. 5. Now your r2 or R1 + R2 reading is the circuit, not the leads.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing