Nine worked codes

From Best Practice Guide 4. Work through them before looking at the right-hand column.

#ObservationCode
1Main protective bonding conductor on a TN system is 4 mm²C2
2Main protective bonding connected to branch pipework, continuity back to the service not assuredC3
3No RCD protection on a lighting circuit in a domestic propertyC3
4Metal socket outlet is live due to a faultC1
5Metallic gas pipe being used as the earthing of the installationC2
6RCD or RCBO on a TT system fails to trip when the test button is pressedC2
7Care home with no AFDD protectionC3
8Consumer unit mounted at height but still accessible for operation, inspection, testing and maintenanceAcceptable — observation only
9Switch line not identified as a line conductor at terminationsNC in the guide — C3 on the report
Number 2 is a C3 — improvement recommended. The main bonding conductor is there; it is just on branch pipework instead of before any branch, so the bond needs moving to the right place. It would be a C2 if the omission made it potentially dangerous.
Number 5 catches people. Using a gas pipe as the earth feels like it should be a C1 — but extraneous metalwork does run to earth, so under normal conditions nothing is dangerous. It is wrong, it is urgent, it is a C2. Same logic as the missing earthing conductor.
Number 7: the guide says C3. BS 7671 (Reg 421.1.7) requires AFDDs on a care home's socket-outlet final circuits up to 32 A — but not meeting the current edition is not in itself unsafe. Code it on what it actually presents, and explain the missing AFDDs plainly in the observation.

Number nine, in detail — because it shows how judgement works

A switch line in blue, with no brown sleeving at the terminations. Nothing is in the wrong terminal; it simply has not been identified.

Can you follow the cable on inspection?CodeWhy
Yes — route is traceable, terminations correctC3Not dangerous. An improvement for clarity and for whoever works on it next
No — route cannot be followedC2You cannot prove it is in the right place, so you cannot say it is safe
✋It becomes dangerous when someone else works on it. An unidentified switch line is a trap for the next person — change a fitting, put the conductor back in the wrong terminal, and the C3 has just become a genuine hazard. That is the argument for sleeving, and it is why the code is not nothing.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside