Mixed-up neutrals on a split-load board: what happensNo earth fault, but both RCDs trip. Why?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
With the board dead, swap the neutrals of the cooker circuit (on RCD 1) and the lighting circuit (on RCD 2) between the two neutral bars. You'd be amazed how many electricians don't know about this. Most learn it the hard way, once.
- Main switch on, both RCDs on, both CBs on: nothing happens, because there's no load yet.
- Turn the light switch on. The lamp flashes, there's a click, and both RCDs trip. Repeat it: both trip again.
- With the board dead, put the neutrals back in the correct bars. Now the light switches on and off and the RCDs are happy.
You've fitted the board, you're handing over to the customer and getting paid, and the RCDs keep tripping. You might think there's a fault, but it can be this simple mistake. Yes, initial verification should have caught it, but if it didn't, check the neutrals are in the right bars before you go hunting for a fault.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing