Metal conduit as the cpc
In a lot of metal installations the actual cpc is the metal conduit — and this is something you may well meet in your practical assessment.
How the earth path runs
Metal conduit, earthed at each end of the run -> into the metal back box (also earthed) -> fly lead from the back box to the front plate -> and the cpc of the twin and earth cable back to the MET
SWA, and circuits with no neutral
The armour of steel wire armoured cable can be used as the cpc.
Using three-core SWA for a single-phase circuit
You sleeve the cores to identify them. Which colour you use for which does not matter — what matters is that both ends match. The conductor that is a neutral at the accessory must land in the neutral bar at the consumer unit.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing