The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
  1. Supply polarity confirmed. Main switch still off and locked.
  2. Disconnect the earthing conductor from the MET. That removes the parallel paths through the bonding and the pipework, so you measure the supply’s earth alone.
  3. Loop impedance setting. Clip one lead to the disconnected earthing conductor, the other on the line terminal on the supply side of the main switch. It’s live: GS38 probes.
  4. Press test. The meter applies a small load for a moment — you may hear it click — and shows the impedance.
  5. Reconnect the earthing conductor. Straight away, before anything else.
Origin line: supply side of the main switch earthing conductor OFF line · tails, meter, cut-out, supply cable PEN (TN-C-S) or sheath (TN-S) back Transformer through the winding to the star point the whole loop = Ze
Everything outside your installation: the supplier’s line conductor out to the transformer, and the earth path back. With the earthing conductor off the MET, nothing of yours is in parallel with it.

What it should read

SystemExpected maximum Ze
TN-C-S (PME)about 0.35 Ω
TN-Sabout 0.8 Ω
✋Rule of thumb, not a hard limit. These are the figures the supplier typically declares.
Two leads or three? Some meters measure Ze with two leads, line and earth. Others want the neutral connected as a third. Learn your own meter.

Ze goes on EIC page 2, in the nature of supply parameters box.

A sensible Ze also lets you tick earthing conductor continuity on EIC page 2. Your lead was on the earthing conductor itself, so the loop you measured runs through it, back to the source.

Electrician’s Guide · p.53 · typical maximum Ze: 0.35 Ω TN-C-S, 0.8 Ω TN-S

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside