Measuring Zdb at the boardWhy test again with the earth reconnected?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: Why test again with the earth reconnected? The answer is in the notes below.
The notes
Exactly as they are on the site.
With the earthing conductor reconnected, repeat the tests at each distribution board other than the main one — a garage, workshop or summer-house board: earth lead on that board’s earth bar, line and neutral as before. Nothing is disconnected, so the parallel paths are in.
- Zdb and the board’s Ipf go at the top of the schedule of test results for that board.
- Zdb is the Zs of the distribution circuit feeding that board, so it takes in that cable as well as the supply. Record what you see.
- For the main board itself, the Zdb box takes your Ze value.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing