Every protective device has a maximum permitted Zs — the highest loop impedance it can still tolerate and disconnect in time. The values are tabulated in Chapter 41, and which table you use depends on the device and the circuit type. This is a classic trap.

TableDevicesCircuitsTime
41.2Fuses — BS 88-2, BS 88-3, BS 3036, BS 1362Final, within 411.3.2.20.4 s
41.3Circuit breakers — BS EN 60898, RCBOsFinal and distribution0.4 s & 5 s
41.4Fuses — same list as 41.2Distribution, and final circuits under 411.3.2.35 s
✋41.2 and 41.4 cover the same fuses. 41.2 is fuses at 0.4 s; 41.4 is fuses at 5 s, for distribution circuits and for final circuits under 411.3.2.3. This exact question catches people out, by sending them to the wrong table. Highlight "0.4 s" and "5 s" in the two headings. Table 41.4 (5 s) is for distribution circuits and for final circuits under 411.3.2.3.

Worked example: "What is the tabulated earth fault loop impedance for a 63 A BS 88-2 (gG) fuse supplying a distribution circuit?" → distribution means 5 s means Table 41.4 → 63 A row → 0.78 Ω.

The ABC trap in Table 41.3

✋Table 41.3 labels its circuit-breaker column groups a, b, c — but those letters mean type B, type C and type D. So column a = type B, b = type C, c = type D. Read the row heading, not the letter, or you'll price a type C answer for a type B question.

Values all from Table 41.3:

DeviceMax Zs (tabulated)
Type B, 16 A2.73 Ω
Type B, 50 A0.87 Ω
Type C, 32 A0.68 Ω
≡The four points to memorise.
1. Every circuit has a Zs.
2. Every circuit has an overcurrent protective device (an OCPD) — not every circuit needs an RCD, but every circuit needs overcurrent protection.
3. Every OCPD has a maximum Zs.
4. If the circuit's Zs does not exceed that maximum, ADS will be achieved.

Table 41.2 · fuses, 0.4 s Table 41.3 · circuit breakers (a = type B, b = type C, c = type D) Table 41.4 · fuses, 5 s (distribution circuits, and final circuits under 411.3.2.3)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside