Max permitted Zs and the 80% figureWhich maximum Zs do you compare against?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: Why do the two Zs columns differ? The answer is in the notes below.
The notes
Exactly as they are on the site.
Two figures for the same circuit, from different books for a reason. Only one goes in the schedule's maximum Zs box.
| Figure | Also called | Comes from | Applies to |
|---|---|---|---|
| Max permitted — the schedule box | Max tabulated | BS 7671 · Tables 41.2–41.4 | The cable in service, warm |
| Max measured — your check value | The 80% value | On-Site Guide Table B6 | The cable cold, as you test it |
BS 7671's figures assume the cable is in use and current has warmed the copper, raising its resistance. On initial verification the cable is cold — nothing has run through it but your test current. The 80% allowance covers the difference.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing