Look before you calculate: the demand against the supply fuseCan you calculate a board you haven't looked at?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
Sum of protective devices130 A — over a 100 A fuse
Maximum demand71.2 A — comfortably inside 100 A, and inside 80 A too

DNO cut-out fuses are typically 80 A or 100 A. If the demand will not fit, the options are to reduce it, to refuse the work, or to ask the DNO for a second phase or a three-phase supply — which is possible and expensive.