Look before you calculate: the demand against the supply fuseCan you calculate a board you haven't looked at?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
| Sum of protective devices | 130 A — over a 100 A fuse |
| Maximum demand | 71.2 A — comfortably inside 100 A, and inside 80 A too |
DNO cut-out fuses are typically 80 A or 100 A. If the demand will not fit, the options are to reduce it, to refuse the work, or to ask the DNO for a second phase or a three-phase supply — which is possible and expensive.