Live-live, live-earth, and the global methodTwo insulation tests per circuit, or three?

Free from the notes: the section word for word as members see it, and a PDF to keep.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

The certificate gives you two boxes, not three. That tells you something.

BoxWhat it means
Live – liveLine to neutral
Lives – earthLine and neutral joined together, tested to the CPC
✋Not line-to-earth and neutral-to-earth as two separate tests. Note the s on "live conductors". You join the line and neutral and test the pair against the protective conductor. That's two tests per circuit, not three.

Three ways to do it, in ascending order of sanity

  1. Pull the conductors out. Disconnect line and neutral from the board and clip your leads onto them. On a ring, remember there are two of each — clamp both, on clean copper, not on the insulation. Slow, and every disconnection is another chance to make a mistake or drop something.
  2. Piggyback leads. A lead with a socket in one end so a second lead can plug into it — turns one lead into two, so you can join line and neutral without pulling them out.
  3. A link lead. A magnetic bridge that sits across the line terminal of the breaker and the neutral, linking them into one test lead. Nothing gets disconnected at all.
The link lead on different devices. On an RCBO the line and neutral are both at the front, so it bridges straight across. On a plain circuit breaker you go from the breaker's line terminal to the neutral bar position serving that circuit. Brass works fine — it's a conductor.

Global insulation resistance

🌐Clip onto the earth bar (or the neutral bar) and the load (busbar) side of the main switch, with all breakers on and the main switch off. You test every circuit at once.

Ten circuits individually means ten rounds of disconnecting, testing and reconnecting. Global does the lot in one. It's a very quick test — the only limit is your battery.

✋All loads must be removed first — and not by you. This is a liability point, not a pedantic one. If you unplug a client's heater and drop it, you are paying for it. Get the client to remove them. That includes lamps — leave a bulb in and the test will show you a fault that isn't there.

GN3 · 2.6.7 · p.68 · insulation resistance figures · global method ★

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside