Insulation resistance: what it proves, and at what voltage500 volts or 250?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
What an insulation resistance test confirms is simple: that the conductors are not touching anywhere inside that cable — that they run the whole way separate from each other. The test is applied across the load.
| Test voltage | Where |
|---|---|
| 500 V d.c. | All installations and circuits rated up to 500 V, except SELV and PELV |
| 250 V d.c. | SELV and PELV circuitry — and anywhere sensitive electronics cannot be disconnected |
A shaver socket is the example you will meet most in domestic work — and it is not SELV. Its isolating transformer gives electrical separation. The supply side, coming in at 230 V, is tested at 500 V, and so is the separation itself: Guidance Note 3 · 2.6.9 · Table 2.15 · p.75 gives 500 V d.c., minimum 1.0 MΩ. You do not drop to 250 V for it.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing