Insulation resistance: three readings, two columnsLine to earth 900, neutral to earth 700. What do you record?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Insulation resistance tester, 500 V. Write the test voltage on the schedule first. Then, for each circuit, three readings:
- Switches closed. A cooker switch left off leaves the cable to the outlet out of the test.
- An RCBO stays off, and you test on its circuit terminals (line and neutral both land on an RCBO). It’s voltage-sensitive.
- Record the lowest reading in each column, exactly as the meter shows it — including the >.
Guidance Note 3 · 2.6.7 · switches closed Guidance Note 3 · 2.6.7 · two-way and intermediate switching
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk