Insulation resistance practical: big numbers this timeOne megohm on a brand new circuit. Pass?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
The last of the main dead tests. Polarity is confirmed after it — mostly proved already by your continuity tests, with Edison screw lampholders checked on their own (except E14 and E27 to BS EN 60238). You are proving the insulation is intact: line not touching neutral, line not touching earth, neutral not touching earth.
So you want big numbers: megohms, millions of ohms. Ideally the tester runs out of range and shows its over-range reading — >999 MΩ on one meter, >200 or >2000 on another. Off the scale is exactly what you want.
| Circuit | Test voltage | Minimum |
|---|---|---|
| SELV and PELV | 250 V DC | 0.5 MΩ |
| Up to and including 500 V (ordinary single and three phase) | 500 V DC | 1 MΩ |
| Above 500 V | 1000 V DC | 1 MΩ |
Guidance Note 3 · 2.6.7 · insulation resistance · from p.68 Guidance Note 3 · 2.6.7 · minimum values; below 20 MΩ on new work · p.70
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing