Installation reference methodsWhy does the same cable carry less current in insulation?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

The reference method describes how and where a cable is installed. This affects how much current it can carry, because heat has to escape. More insulation around a cable means more heat trapped, which means more resistance and a lower current rating. You may then need a bigger cable.

C clipped directto a surface best rating B conduit/trunkingon or in a wall,not insulated A in conduit ina thermallyinsulated wall Rule A vs B: the onlydifference is whetherthe wall is insulated. Mixed methods on onerun? Size for theworst case. 100 T&E on joist,insulation ≤100 mm 101 same, butinsulation >100 mm 102 stud wall, touchinginner wall surface 103 surrounded by insulation ≥0.5 m: half the rating
Simplified sketches. Methods 100–103 apply to flat twin and earth (thermoplastic, PVC/PVC, 70 °C). "Multicore flat cable" is another name for T&E. Method C (clipped direct) gives the highest current rating.
  • A cable surrounded by thermal insulation for a short length is derated by its length (cables up to 10 mm², BS 7671 Appendix 4, section 2.6, p.451): 50 mm → 0.88, 100 mm → 0.78, 200 mm → 0.63, 400 mm → 0.51. Totally enclosed for 0.5 m or more means the rating is half that of clipped direct (0.5).
  • Examples from the table: 1.0 mm² T&E clipped direct = 16 A (enclosed in insulation, about half), and 2.5 mm² clipped direct = 27 A. The rating drops for method B and the 100-series methods.
  • PVC-sheathed cable must not touch polystyrene, which degrades it over time.
  • Twin and earth can go in conduit or mini-trunking for extra protection. Councils often run mini-trunking along skirting and ceilings instead of chasing. But more cables bunched together means more heat.

Electrician's Guide to the Building Regs · 2.3.1 Cable installation methods A, B, C Electrician's Guide to the Building Regs · Reference methods 100, 101, 102, 103 · pp.39–41 Electrician's Guide to the Building Regs · Table 2.3.1 T&E current ratings · p.41 BS 7671 · Appendix 4 · section 2.6 · cables surrounded by thermal insulation · p.451

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside