Ia: the current the device needs to operate
This is the one people get backwards. For a Type B circuit breaker, the current required to operate it in the required time is five times its rating:
Reading it off the table
6 A Type B -> 5 × 6 = 30 A 20 A Type B -> 5 × 20 = 100 A 32 A Type B -> 5 × 32 = 160 A
The time/current graphs
The table above is not something to memorise — it is printed. Known as "the graphs of doom": BS 7671 · Appendix 3, time/current characteristics for Type B circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009-1.
Beside the curves is a table giving the current required for 0.1 s to 5 s:
| Rating | Current | Rating | Current |
|---|---|---|---|
| 6 A | 30 A | 40 A | 200 A |
| 10 A | 50 A | 50 A | 250 A |
| 16 A | 80 A | 63 A | 315 A |
| 20 A | 100 A | 80 A | 400 A |
| 25 A | 125 A | 100 A | 500 A |
| 32 A | 160 A | 125 A | 625 A |
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing