Ia: how fast the device disconnectsHow many amps blow a 20 amp fuse in 0.4 seconds?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
What it's for: using the PEFC to find how long the protective device takes to disconnect. Ia is the current that makes the device operate within a given time. It isn't a calculation as such. You read it from the time/current curves (and the tables beside them) in Appendix 3 of BS 7671.
Our example is a piece of 20 A BS 3036 fuse wire (a rewireable fuse). The wire has to get hot enough to melt, and that depends on the current through it. In normal use it mustn't blow ("melt, melt, blow, oh no, replace the fuse wire!"). But in an earth fault (a low-impedance path to earth, high current, parts live that shouldn't be) we want it to melt, and quickly.
| 20 A BS 3036 fuse (values used here) | 0.1 s | 0.2 s | 0.4 s | 1 s | 5 s |
|---|---|---|---|---|---|
| Ia needed to disconnect in that time | 260 A | 180 A | 130 A | 92 A | 60 A |
- The circuit's maximum disconnection time is 0.4 s, so the fuse needs at least 130 A.
- Only 50 A? It takes longer than 5 s. Only 70 A? Somewhere between 1 and 5 s, probably about 3 s.
- 500 A? Well under 0.1 s. Very quick.
So the rule is: the more current, the faster it trips or blows. Every circuit has a maximum disconnection time, and if the fault current doesn't reach Ia, the device won't operate in time.
BS 7671 · Appendix 3 · time/current characteristics · BS 3036 semi-enclosed (rewireable) fuses · check your copy for the page BS 7671 · Appendix 3 · Fig 3A4 Type B circuit-breakers · p.445
Another example: would the 20 A fuse do?
PEFC (section 11 example) = 291.3 A Table above: 260 A → 0.1 s 291.3 A > 260 A → disconnects in under 0.1 s ✓ (well inside 0.4 s)
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing