Picture a BS EN 61008 RCD, a Type AC. You'll hear "it's got an RCD" or "just put an RCD on it" a lot in the trade. Often that shows the person doesn't really understand what an RCD does.
The question isn't whether there's an RCD. It's which job the RCD is doing and what rating that job needs. That's what this masterclass is about.
There are different types of RCD (AC, A, F and B). These notes only touch on them at the end (see section 10). The main focus is when to use one and what size.
Everything here applies to any device that contains an RCD. An RCBO counts, because it's an RCD and a circuit breaker in one unit. So do RCD socket-outlets and RCD fused connection units.
BS EN 61008 · RCCB (RCD without overcurrent protection) · BS EN 61009 · RCBO
How an RCD works
Inside every RCD or RCBO is a toroid coil, a ring-shaped core that the line and neutral both pass through. The most common rating is 30 mA, which is 0.03 A.
Start with the simplest possible circuit: a supply transformer and its star point, an RCD, and a load. It's TN-S, but the system type doesn't matter for how the RCD works. The meter, main switch and consumer unit are left out to keep the RCD as the focus.
Balanced line and neutral
Say the load draws 10 A. Using the power triangle the other way round, that's 230 × 10 = 2.3 kW. So 10 A goes out on the line and 10 A comes back on the neutral. This is Kirchhoff's current law (Gustav Kirchhoff, 19th-century physicist): whatever goes out on the line comes back on the neutral.
The RCD works like a see-saw. It compares line and neutral. While they're equal it stays balanced. If the neutral suddenly carries less than the line, it's out of balance and it trips.
Current doesn't just disappear. If 10 A goes out and less than 10 A comes back, the difference has found another path to earth, for example through an exposed-conductive-part that has become live. That's why people say RCDs protect against electric shock.
How that's different from a fuse or circuit breaker
Fuses, fuse wire and circuit breakers also disconnect during an earth fault, but they rely on a very low impedance between the exposed-conductive-part and the star point. Low impedance means a high fault current, and that high current blows the fuse or trips the breaker.
RCDs are more sophisticated. They don't need a big fault current. They only look at whether line and neutral are equal, so they can be very sensitive.
Worked example: the football and the outside light
Outside light on the side of a house, still drawing 10 A (to keep the numbers simple) Kids kick a football at it and crack the glass slightly Moisture gets in and reaches the connections Leakage to earth = 0.03 A (30 mA) Line = 10 A Neutral = 10 − 0.03 = 9.97 A Imbalance = 0.03 A = the RCD's rating → it trips
A common assumption is that anything less than the rating (for example 0.02 A) shouldn't trip it. But RCDs can be very sensitive, and a 30 mA RCD you buy may well trip before it reaches 30 mA of imbalance. A ramp test shows exactly where it trips.
The product standards say a 30 mA RCD must not trip at half its rating (15 mA) and must trip at its full rating (30 mA). Anywhere between 15 and 30 mA is allowed. So a 30 mA RCD tripping at 20 mA is normal, not a fault. That's the "sensitive" behaviour described above, and the ramp test finds the exact point.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing