Gardens and outbuildingsHow deep does a buried garden cable go?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: How deep does a buried garden cable go? The answer is in the notes below.
The notes
Exactly as they are on the site.
- Bury garden cables at least 500 mm deep, preferably deeper, and at least 600 mm where "double digging" is likely, such as a vegetable plot. About 2 ft (600 mm) is the usual.
- Lay marker tape or cable tiles about 150 mm below the surface along the route, so a spade hits the warning first.
- Use SWA (armoured) or a metal-sheathed cable, or run it in a conduit or duct (like a flexible hoover pipe). Bedding it in sifted sand is common practice. Burying is best practice, but SWA clipped along a fence or wall is also used.
- Mark the route with route markers and record it on the drawings kept with the EIC, so the next person knows where it runs.
- What BS 7671 says (Reg 522.8.10): no depth is given. Unless it is in a conduit or duct giving equivalent mechanical protection, a buried cable needs an earthed armour or metal sheath suitable for use as a protective conductor. Its route is marked with cable covers or marker tape, and it goes deep enough to avoid damage from any reasonably foreseeable disturbance of the ground. The depths above come from the Electrician's Guide, not BS 7671.
- Outbuildings (sheds, garages) are usually fed from the house consumer unit to a small distribution board in the outbuilding, with its own switch and sockets.
Electrician's Guide to the Building Regs · 5.7.2 fixed cables: buried cables in gardens (depth, marker tape) · p.96 BS 7671 · Reg 522.8.10 buried cables · p.153 Electrician's Guide to the Building Regs · Figure 5.7.3 outbuilding supply · p.97
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing