Finding a fault — and where you restartAfter a fix, where do you restart your tests?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Take that ring with the high neutral reading. Working the fault out is a better lesson than any diagram.
| Test | Result |
|---|---|
| Continuity, line and CPC | Good — r1 0.01 Ω and r2 0.02 Ω, as expected |
| Insulation resistance, live conductors to earth (line and neutral joined, to CPC, global) | > 2000 MΩ — good |
| Continuity, neutral end to end | 0.52 Ω against 0.01 Ω on the line — outside the 0.05 Ω tolerance |
| Insulation resistance, line to neutral (global) | Fail |
What it's likely to be: a conductor slipped out of a terminal and touching something it shouldn't, a high-resistance joint, or damaged insulation with bare copper in contact somewhere.
The question that catches people
GN3 · 2.6 · Figure 2.12 · p.57 · the sequence of tests ★ OSG · Section 10
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing