The notes
Exactly as they are on the site.
One per distribution board. A shed sub-board fed from the house board gets its own, and its “supplied from” is the house board, not the mains.
The top of the sheet: the board
Board reference and location, what it’s supplied from, the overcurrent device feeding it, the SPD type (T1, T2, T3 or N/A), and the RCD details if the board has one protecting everything.
One row per circuit
| Column | What goes in it |
|---|---|
| Circuit number and description | Every way on the board. Spares get a line drawn through, so nobody can add to the sheet later |
| Type of wiring | A code from the key at the bottom of the form (below) |
| Reference method | From BS 7671 Table 4A2: e.g. C clipped direct, B in conduit or trunking on a wall, 100–103 for twin and earth run through thermal insulation in ceilings or stud walls |
| Number of points served | The points of utilization on the circuit: sockets, luminaires, outlets |
| Live and CPC csa | e.g. 2.5 / 1.5 for a ring in twin and earth |
| Overcurrent device | BS (EN) number, type, rating, and breaking capacity in kA |
| Maximum permitted Zs | From the BS 7671 tables: B32 is 1.37 Ω, B6 is 7.28 Ω |
| RCD | BS (EN) number, type, IΔn and rating — or N/A if the circuit has none |
| Code | Wiring |
|---|---|
| A | Thermoplastic insulated and sheathed cables (twin and earth) |
| B | Thermoplastic cables in metallic conduit |
| C | Thermoplastic cables in non-metallic conduit |
| D | Thermoplastic cables in metallic trunking |
| E | Thermoplastic cables in non-metallic trunking |
| F | Thermoplastic SWA |
| G | Thermosetting SWA |
| H | Mineral insulated |
| O | Other — say what |
A circuit run in more than one wiring system gets more than one code.
A Type 3 SPD fitted to protect sensitive equipment goes in the Remarks column.
Guidance Note 3 · Fig 5.3 · p.149 · an example schedule BS 7671 · Table 41.3 · max Zs, circuit-breakers BS 7671 · Appendix 4 · Table 4A2 · reference methods
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing