Filling in EIC page 2: supply, earthing and the main switchIs maximum demand the main fuse?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The question at the end: Is maximum demand the main fuse? The answer is in the notes below.
The notes
Exactly as they are on the site.
This is the general characteristics — what an inspector has to know before inspecting anything. Most of it is ticks.
| Box | What goes in it |
|---|---|
| Earthing arrangement | TN-C, TN-S, TN-C-S (PME), TN-C-S (PNB), TT or IT. On the A4 form, TN-C-S is split into PME and PNB |
| Live conductors | AC or DC, then the wires. Single phase is 1-phase, 2-wire (line and neutral both count). Three phase with a neutral is 3-phase, 4-wire |
| Nominal voltage, frequency | 230 V (or 400/230 V three phase) and 50 Hz. These are by enquiry |
| Prospective fault current, Ze | By enquiry or measurement. Both are live tests — leave them empty until you’ve done them |
| Supply protective device | The DNO’s cut-out fuse, read off the front: e.g. BS 1361, Type II, 100 A |
| Means of earthing | The distributor’s facility, or an installation earth electrode (with its type, location and resistance) |
| Maximum demand | See below |
| Earthing conductor | Material and size, e.g. copper 16 mm². A tick for “connection / continuity verified” comes later |
| Main protective bonding | Material and size, e.g. copper 10 mm², and what it bonds: water, gas, oil, structural steel, lightning protection, other |
| Main switch | Location, BS (EN) number, number of poles, current rating, voltage rating |
Maximum demand isn’t the main fuse
It’s tempting to write the cut-out rating (“it’s a 100 A fuse, so 100 A”) or the main switch rating. Guidance Note 3 says what it actually is: the maximum demand expressed in amps, kW or kVA, after diversity is taken into account. The form says “kVA / A”, so delete whichever you’re not using. The fuse rating already has its own box.
The main switch: isolator or circuit-breaker?
A domestic main switch is normally BS EN 60947-3: a switch-disconnector. The 100 A on the front is what it can switch on load. It doesn’t protect anything. So the form’s “if overcurrent protective device” block is N/A, and so is the “if RCD main switch” block, unless the main switch really is an RCD. A main switch to BS EN 60947-2 is a circuit-breaker, and then its rating and breaking capacity go in that block. Two poles on single phase (line and neutral), more on three phase.
Boxes you leave empty for now
| Box on page 2 | Filled in after |
|---|---|
| Main bonding: continuity verified | Testing continuity of the main bonding |
| Confirmation of supply polarity | The live supply polarity check |
| Prospective fault current · Ze | The live tests at the origin |
| Earthing conductor: continuity verified | A sensible Ze, taken with your lead on the earthing conductor itself, shows the earth path is continuous all the way back to the source |
Guidance Note 3 · 2.3 · required information, max demand Guidance Note 3 · Fig 5.2 · p.148 · an example page 2 BS EN 60947-3 · the main switch
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing