Electrical formulas: a quick-reference tableUseful calculations, in a minute.

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Every calculation from this masterclass, in the order a designer uses them.

CalculationFormulaUse it when…Where
Design current (single-phase)Ib = P ÷ VYou need the circuit's current from the load. V = the voltage present at the origin of the circuit (usually 230 V).Power triangle
Design current (three-phase)Ib = P ÷ (√3 × VL)Three-phase load. VL = 400 V. Answer is per phase.√3 = 1.73
Tabulated current neededIt ≥ In ÷ (Ca × Cg × Ci …)Sizing a cable. Only use the factors happening at the same time.BS 7671 App 4 · Tables 4B1, 4C1, 2.6
Cable sizetable value ≥ ItRead down your cable's A table, in the column for your method.BS 7671 Appendix 4 cable tables
Voltage dropVD = mV/A/m × Ib × L ÷ 1000Checking there's enough "push" left. Limits 3% / 5%.B tables · Table 4Ab
R1 + R2 (designer)B1 × B3 × L ÷ 1000Designing for an earth fault (conductors at operating temperature).GN3 Tables B1, B3
R1 + R2 (ring)(r1 + r2) ÷ 4Ring final circuits. r = single conductor end to end (the "dash" rows).GN3 Table B1 (+ B3 or B2)
R1 + R2 (inspector)B1 × B2 × L ÷ 1000Correcting a measured value to the ambient temperature on the day. Never in a design.GN3 Table B2 p.175
Earth fault loopZs = Ze + (R1 + R2)Checking ADS. Ze by measurement, enquiry or calculation (or given).Compare with max Zs (Ch 41)
Prospective earth fault currentPEFC = U₀ × Cmin ÷ ZsHow many amps flow in an earth fault. Cmin = 0.95 (218.5 V).Ohm's law, worst case
Ia / disconnection timeread from the curvesHow fast the device operates at that PEFC (more amps = faster).BS 7671 Appendix 3
AdiabaticS = √(I² × t) ÷ kChecking the CPC can carry the fault current until the device operates.k: Chapter 54 (Table 54.3 = 115)

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside