Electrical formulas: a quick-reference tableUseful calculations, in a minute.
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Every calculation from this masterclass, in the order a designer uses them.
| Calculation | Formula | Use it when… | Where |
|---|---|---|---|
| Design current (single-phase) | Ib = P ÷ V | You need the circuit's current from the load. V = the voltage present at the origin of the circuit (usually 230 V). | Power triangle |
| Design current (three-phase) | Ib = P ÷ (√3 × VL) | Three-phase load. VL = 400 V. Answer is per phase. | √3 = 1.73 |
| Tabulated current needed | It ≥ In ÷ (Ca × Cg × Ci …) | Sizing a cable. Only use the factors happening at the same time. | BS 7671 App 4 · Tables 4B1, 4C1, 2.6 |
| Cable size | table value ≥ It | Read down your cable's A table, in the column for your method. | BS 7671 Appendix 4 cable tables |
| Voltage drop | VD = mV/A/m × Ib × L ÷ 1000 | Checking there's enough "push" left. Limits 3% / 5%. | B tables · Table 4Ab |
| R1 + R2 (designer) | B1 × B3 × L ÷ 1000 | Designing for an earth fault (conductors at operating temperature). | GN3 Tables B1, B3 |
| R1 + R2 (ring) | (r1 + r2) ÷ 4 | Ring final circuits. r = single conductor end to end (the "dash" rows). | GN3 Table B1 (+ B3 or B2) |
| R1 + R2 (inspector) | B1 × B2 × L ÷ 1000 | Correcting a measured value to the ambient temperature on the day. Never in a design. | GN3 Table B2 p.175 |
| Earth fault loop | Zs = Ze + (R1 + R2) | Checking ADS. Ze by measurement, enquiry or calculation (or given). | Compare with max Zs (Ch 41) |
| Prospective earth fault current | PEFC = U₀ × Cmin ÷ Zs | How many amps flow in an earth fault. Cmin = 0.95 (218.5 V). | Ohm's law, worst case |
| Ia / disconnection time | read from the curves | How fast the device operates at that PEFC (more amps = faster). | BS 7671 Appendix 3 |
| Adiabatic | S = √(I² × t) ÷ k | Checking the CPC can carry the fault current until the device operates. | k: Chapter 54 (Table 54.3 = 115) |
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing