Earthing systems: TN-S, TN-C-S, TTTN-S, TN-C-S or TT. How does fault current get home?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Every building is supplied from a transformer, and every transformer has a star point. That star point is the source of earth for the installation. Fault current has to get back to the star point for the protective devices to work. How it gets back depends on the earthing system.

TN-Sstar pointhomeMETcable sheathZe max 0.8 Ωseparate N and E all the wayTN-C-S (PME)star pointhomeMETPENPMErodsZe max 0.35 ΩPEN: N + E combined, split at cut-outTTstar pointhomeMETrodfault path via the groundZe up to about 200 Ωyour own earth electrode, no supplier earth
Simplified: the star point is on the left of each drawing and the home is on the right. TN-S and TN-C-S are the focus here; TT is shown for comparison.
SystemHow the earth gets back to the star pointMax Ze
TN-SNeutral and earth are separate all the way. The earth is the metal sheath or armour of the supply cable. Common in older properties.0.8 Ω
TN-C-S
also called PME
Neutral and earth are combined in the underground supply cable, in one conductor called the PEN conductor (protective earth neutral). They're separated at the cut-out. It's the most common system in the UK, very reliable, with very low resistance to earth.0.35 Ω
TTNo earth from the supplier. The installation has its own earth electrode (rod), and fault current returns through the ground. Used in rural areas.up to about 200 Ω (your own electrode)

Our first installations are drawn as TN-S, but it makes no difference to the bonding rules whether it's TN-S or TN-C-S. The difference only matters for open PEN faults (section 8), which can only happen on TN-C-S.

Electrician's Guide to the Building Regs · Supply systems: expected maximum Ze values (TN-C-S 0.35 Ω, TN-S 0.8 Ω) · p.53

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside