Earthing systems: TN-C-S, TN-S, TTTN-C-S, TN-S, TT. What do the letters mean?

Free from the notes: the section word for word as members see it, and a PDF to keep.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Reading the letters: T = Terra (earth) · N = Neutral · C = Combined · S = Separate.

SystemHow the earth is providedExpected max ZeWhere you'll find it
TN-C-S
also called PME
Neutral and earth are combined in the supply cable (PEN conductor), then separated at the cut-out. PME = protective multiple earthing, with many earth connections along the network. Provided by the DNO.0.35 ΩMost new builds and most homes today
TN-SEarth and neutral are separate all the way. The earth is the metal sheath or armour of the supply cable, clamped and taken to the MET. Provided by the DNO.0.8 ΩOlder properties
TTNo earth from the DNO. The installation has its own earth electrode (rod or plate) in the ground. The client pays for it, and you install it.up to 200 ΩRural areas, farms, caravan parks and other places too far from a transformer's star point
TN-C-S (PME) transformerproperty PEN (N + E) split at cut-out Ze ≤ 0.35 Ω TN-S cable sheath / armour = earth Ze ≤ 0.8 Ω TT own earth electrode (client pays) Ze up to 200 Ω
Simplified. The transformer's star point is on the left of each drawing and the property on the right. TT has a much higher Ze because the fault current has to travel back through the ground between two earth rods.

Electrician's Guide to the Building Regs · Supply systems: expected maximum Ze values (TN-C-S 0.35 Ω, TN-S 0.8 Ω) · p.53 Electrician's Guide to the Building Regs · Figure: cable sheath earth (TN-S), earthing and main bonding · p.55 On-Site Guide · List of earth electrode types (rods, plates, etc.) for TT

The earth fault path

Suppose a line conductor comes loose and touches the metal case of a load. The fault current travels through the case, along the CPC to the MET, down the earthing conductor, back through the supply to the transformer star point, and round to the protective device, which trips. This is automatic disconnection of supply (ADS).

Earth is not a current-carrying conductor under normal conditions. It only carries current when there's an earth fault. For ADS the circuit breaker or fuse must disconnect within the Table 41.1 time (0.4 s on a TN final circuit). Where an RCD gives the protection, a non-delayed RCD must trip within 300 ms at its rated residual current.
Why TN-C-S has a risk
Because the neutral and earth are combined in the supply cable, damage to that PEN conductor (a nick or a cut) means more than losing your earth: all the earthed and bonded metalwork in the installation can rise towards line voltage. On TN-S, a problem with the sheath earth only affects that one property, so it's easier to spot. On your own circuits, you can use the armour of SWA cable as the CPC.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside