Earthing systems and ZeTN-C-S, TN-S or TT. What Ze should you expect?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
| System | Key point | Expected max Ze |
|---|---|---|
| TN-C-S (PME) | Neutral and earth combined in the supply (the PEN conductor, protective earth neutral), separated at the cut-out | 0.35 Ω |
| TN-S | Earth and neutral separate the whole way, with the earth via the cable sheath | 0.8 Ω |
| TT | Earth electrode, provided and paid for by the client. Ze is high because of ground conditions: a metal rod in the general mass of earth. Above 200 Ω the earth connection becomes unstable. | up to 200 Ω |
Electrician's Guide to the Building Regs · maximum Ze values: 0.35 Ω TN-C-S, 0.8 Ω TN-S · p.53
Ze only measures the external earth path, from the transformer to the incoming MET or consumer unit. Under a fault the circuit breaker should disconnect within the Table 41.1 time (0.4 s on TN, 0.2 s on TT, for final circuits) and a 30 mA RCD trip in 300 ms.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing