Earthing systems and ZeTN-C-S, TN-S or TT. What Ze should you expect?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
SystemKey pointExpected max Ze
TN-C-S (PME)Neutral and earth combined in the supply (the PEN conductor, protective earth neutral), separated at the cut-out0.35 Ω
TN-SEarth and neutral separate the whole way, with the earth via the cable sheath0.8 Ω
TTEarth electrode, provided and paid for by the client. Ze is high because of ground conditions: a metal rod in the general mass of earth. Above 200 Ω the earth connection becomes unstable.up to 200 Ω

Electrician's Guide to the Building Regs · maximum Ze values: 0.35 Ω TN-C-S, 0.8 Ω TN-S · p.53

Ze only measures the external earth path, from the transformer to the incoming MET or consumer unit. Under a fault the circuit breaker should disconnect within the Table 41.1 time (0.4 s on TN, 0.2 s on TT, for final circuits) and a 30 mA RCD trip in 300 ms.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside