Earth rods, the deviation calculation, and RA80, 82 and 84 ohms. What's the deviation?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The question at the end: 80, 82 and 84 ohms. What's the deviation? The answer is in the notes below.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Earth rods, and the three methods again

The rod itself is a threaded bar driven into the ground with a cover at the top. It can be as long as it needs to be — one metre, two, five — and rods can be coupled together to go deeper.

Soil decides. Hard ground that still needs a TT system may mean driving in several.
MethodIn a sentence
E1The most accurate — and hard graft in difficult soil
E2More accurate if there are a number of earth electrodes; the clamp needs at least one other earth path
E3An earth fault loop impedance test. The easiest, and the one you will do — but it may not be as accurate as a dedicated earth electrode tester
Easiest is not most accurate. E3 being the common choice does not make it better than E1.

The deviation calculation

Guidance Note 3 · p.79. This is the step after it, and it is the part that gets skipped.

Three readings: 64, 62.5 and 65.3 Ω

Step 1 — the average
  64 + 62.5 + 65.3 = 191.8
  191.8 ÷ 3 = 63.93 Ω
✋If you got 191.8, you forgot to divide by three. An average is the total divided by how many readings you took.

Step 2 — the percentage deviation

Find the reading furthest from the average.
Here that is 62.5 (1.43 below), not 65.3 (1.37 above):

  63.93 − 62.5   = 1.43
  1.43 ÷ 63.93  = 0.0224
  0.0224 × 100  = 2.24% → 2.2%

Step 3 — the 1.2 factor

Guidance Note 3: the accuracy of a method E1 measurement is
typically 1.2 × the percentage deviation you calculated.

  2.24% × 1.2 = 2.69% → 2.7%
Which reading will be highest, and why. Test 1 is taken at the centre. Test 2 moves the voltage spike towards the electrode by 10% of the full electrode-to-current-spike distance (current spike at 30 m: move 3 m), so you expect a lower resistance. Test 3 moves it the same distance the other way, so you expect a slightly higher one — which is usually your highest figure.
Three readings 64 62.5 65.3 62.5 is furthest from the average 1 average = (64 + 62.5 + 65.3) ÷ 3 = 191.8 ÷ 3 = 63.93 Ω ✋ if you got 191.8, you forgot to divide by three 2 gap ÷ average = (63.93 − 62.5) ÷ 63.93 = 0.022 → 0.022 × 100, so the spread is 2.2% Limit is 5% — 2.2% passes. Above 5% and the spikes move further out, then you test again.
This is the step after it, and it is the one people skip — the average on its own tells you nothing about whether the three readings agreed.

RA: the electrode result, and where it goes

Method E1 gives you an RA result — unless it has been handed to you as a Ze, in which case take it as RA.

RA = the electrode plus the earthing conductor back to the MET

A second worked deviation, with cleaner numbers

Readings: 80, 82, 84 Ω

Average  = 246 ÷ 3 = 82 Ω
Furthest   = 80 and 84, both 2 away
Deviation  = 2 ÷ 82 = 0.024  →  2.4%

Always use the reading furthest from the average.
Where it goes on the EIC. On page 2, tick earth electrode as the means of earthing and TT as the nature of earthing, name the electrode (earth rod, copper rod), and find the field marked RA or Ze — cross out the one that does not apply and write your value in.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside