Earth fault loop impedanceWhat is Zs, and why does it matter?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

For ADS to work, enough fault current has to flow to trip the device within that disconnection time. What limits the fault current is the impedance of the loop it travels round.

Zs = Ze + (R1 + R2)
Ze = the external part, transformer to your origin · R1 + R2 = line plus CPC of your own circuit, from a continuity test
supply 50 A type B load R1 · line R2 · CPC back to earth Ze earth fault the whole loop = Zs
The fault current leaves on the line conductor, through the fault, and returns through the CPC to earth. Everything it travels through, inside and outside the installation, adds up to Zs.
↓You want Zs LOW. Low impedance means a big fault current, and a big fault current trips the device fast. A high Zs means a feeble fault current that may take far too long to operate the breaker — and the exposed metalwork stays live while someone is touching it.

Ze is the external part — the bit between the transformer and your consumer unit. The expected maximum values are given in the Electrician's Guide to the Building Regulations (p.53): 0.8 Ω for a TN-S system and 0.35 Ω for TN-C-S. Measure above that on a live test and you investigate — Guidance Note 3 notes that slightly higher readings are occasionally seen, and that comparing against previous readings tells you more than the number on its own. An unexplained high Ze is the distributor's to fix, not something you design around.

Zs vs Ze in one line. Ze is everything outside your installation. Zs is Ze plus your own circuit's R1 + R2. Every circuit has its own Zs.

How much current does it take to trip?

A type B circuit breaker needs between 3 and 5 times its rated current to trip in the fast part of its curve — and you always design to the worst case, 5 times.

50 A type B × 5 = 250 A of fault current needed

A 6 A type B needs 6 × 5 = 30 A. That's where those multipliers in the On-Site Guide come from, and why a high-Zs circuit is dangerous: it can't deliver the current its own breaker needs.

Zs = Ze + (R1 + R2) Electrician's Guide · p.53 · expected max Ze · TN-S 0.8 Ω · TN-C-S 0.35 Ω On-Site Guide · Section 7 · Table 7.2.7 · trip current multipliers

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside