Earth electrode testing: E1, E2 and E3E1, E2 or E3. Which ones are live?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The question at the end: E1, E2 or E3. Which ones are live? The answer is in the notes below.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Guidance Note 3 · 2.6.13 · pp.78–83 (E1 p.78, Figure 2.26 p.79, E2 p.80, E3 p.83). Three methods, and the thing to remember is that they are not all dead tests.

MethodWhat you doDead or liveAccuracy
E1Test directly on the electrode. A dead test: the earthing conductor is disconnected.DeadMost accurate
E2Clamp around the earthing conductor — single-coil or two-coil. The conductor stays connected to the MET and the other rods stay in, so the supply can stay on. Then apply the formula.LiveMore accurate if there are a number of earth electrodes
E3An earth fault loop impedance test — effectively a Ze test, taken at the incoming supply. Main switch off and the earthing conductor disconnected, usually at the MET — but your leads are on the live supply side.LiveMay not be as accurate as a dedicated earth electrode tester
E3 is the one you will actually do. Most testers do it natively, so there is little reason to spend hundreds on dedicated kit you might use once a year. E1 is the most accurate, but E3 is the common one.
When is E2 the better choice? Guidance Note 3 says method E2 is more accurate if there are a number of earth electrodes (Guidance Note 3 · 4.6 · p.139). The clamp also needs at least one other electrode or earth path for the test current to return through. The book does not rank E2 against E3.
Two likely questions. How many methods are there for testing an earth electrode; and what type of test does method E3 use.
E1 directly on the electrode earthing conductor OFF DEAD test most accurate E2 clamp round the conductor stays connected to the MET LIVE test needs another earth path E3 loop tester at the origin no spikes, no ground needed LIVE test the one you will use ✋ They are not all dead tests. Only E1 is — and that is the one the exam likes to ask about.
E1 is the most accurate: a dead test, with the earthing conductor disconnected. E3 needs no test spikes, which is why it is the common one on site.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside