Earth continuity, and working out the expected resistanceWhat's the most an extension lead can read?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Earth continuity

?Continuity asks: is the protective conductor unbroken from the earth pin of the plug all the way to the accessible metal part? You want a complete path with very low resistance.
✋Class I only. A class II appliance has no earth, so there is no continuity test to do — a dedicated PAT tester set to class II won't even offer it. Extension leads get their own treatment, because class I equipment can be plugged into them.

The limits, from Section 10:

EquipmentMaximum
No supply cable0.1 Ω
With a supply cable (including extension leads and trailing sockets)0.1 Ω + R of the cable
3-core lead sets and extension leads0.1 Ω + R
Multiway adaptors and RCD adaptors0.1 Ω
"Supply cable" means the lead from the plug to the appliance — the bit you'd coil up to carry it.

In practice you put one probe on an exposed-conductive-part — the metalwork itself, not the protective conductor connection point such as the earth screw head. On a class I kettle that's the element housing; on a hot plate, the metal casing or trim. Where there are several, test each. Only exposed-conductive-parts need testing.

Flex the cable while you watch the reading. A value that jumps or climbs points to a poor connection. Painted or powder-coated parts can read high — repeat the test to get a better contact (10.5.2, Table 10.1 notes).

Section 10 · 10.5.2 · protective conductor continuity Table 10.1 · the 0.1 Ω rule

earth pin plug socket at the far end protective conductor — must be unbroken line and neutral run alongside tester measures across the whole length R of the cable
Class I only. An extension lead is tested end to end — earth pin of the plug to the earth contact of the socket — so the reading includes the resistance of the whole cable.

Working out the expected resistance

This is the one calculation in the module, and it's worth having cold.

R = (mΩ/m × length) ÷ 1000
Divide by 1000 because the table is in milliohms per metre — exactly like volt drop and mV/A/m

The mΩ/m figure for the cable is given in the question. The worked examples here use these figures:

CSAmΩ/m
1.25 mm²15.6
2.5 mm²8
4 mm²5
16 mm²1.2

A 12 m extension lead in 1.25 mm²

R = (15.6 × 12) ÷ 1000
R = 187.2 ÷ 1000
R = 0.187 Ω

Maximum permitted = 0.1 + 0.187 = 0.287 Ω

So your measured result should fall
between 0.187 Ω and 0.287 Ω

Two more, worked the same way

15 m of 4 mm²
R = (5 × 15) ÷ 1000 = 0.075 Ω
Maximum = 0.075 + 0.1 = 0.175 Ω

75 m of 16 mm²
R = (1.2 × 75) ÷ 1000 = 0.09 Ω
Maximum = 0.09 + 0.1 = 0.19 Ω
You work it out for one conductor, not two. Where a flex is marked "2 × 0.5", that means line and neutral are each 0.5 mm² — it isn't telling you to double anything. Earth continuity is measured along the protective conductor only — earth pin to the metalwork — so R is for that one conductor.
How do you know the CSA on site? It's printed or embossed on the cable. Also on the drum label and the wrapping.
Extension leads have a maximum length too. Table 10.3 (p.75): 12 m in 1.25 mm², 15 m in 1.5 mm². On a lead, polarity is checked by continuity as well (10.10(d), p.75).

Section 10 · Table 10.1 · p.71 · add 0.1 Ω Table 10.3 · extension lead lengths · p.75

12 m extension lead, 1.25 mm² — 15.6 mΩ/m R = (15.6 × 12) ÷ 1000 = 0.187 Ω · maximum = 0.1 + 0.187 = 0.287 Ω 0.187 Ω 0.287 Ω the cable itself + 0.1 Ω allowance below — check your figures PASS FAIL A reading under 0.187 Ω cannot be right for this cable — recheck the length, the CSA, or whether the leads were nulled.
The answer is a band, not a single number: at or above the cable’s own resistance, and no more than 0.1 Ω above it.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside