Earth continuity
The limits, from Section 10:
| Equipment | Maximum |
|---|---|
| No supply cable | 0.1 Ω |
| With a supply cable (including extension leads and trailing sockets) | 0.1 Ω + R of the cable |
| 3-core lead sets and extension leads | 0.1 Ω + R |
| Multiway adaptors and RCD adaptors | 0.1 Ω |
In practice you put one probe on an exposed-conductive-part — the metalwork itself, not the protective conductor connection point such as the earth screw head. On a class I kettle that's the element housing; on a hot plate, the metal casing or trim. Where there are several, test each. Only exposed-conductive-parts need testing.
Section 10 · 10.5.2 · protective conductor continuity Table 10.1 · the 0.1 Ω rule
Working out the expected resistance
This is the one calculation in the module, and it's worth having cold.
Divide by 1000 because the table is in milliohms per metre — exactly like volt drop and mV/A/m
The mΩ/m figure for the cable is given in the question. The worked examples here use these figures:
| CSA | mΩ/m |
|---|---|
| 1.25 mm² | 15.6 |
| 2.5 mm² | 8 |
| 4 mm² | 5 |
| 16 mm² | 1.2 |
A 12 m extension lead in 1.25 mm²
R = (15.6 × 12) ÷ 1000 R = 187.2 ÷ 1000 R = 0.187 Ω Maximum permitted = 0.1 + 0.187 = 0.287 Ω So your measured result should fall between 0.187 Ω and 0.287 Ω
Two more, worked the same way
15 m of 4 mm² R = (5 × 15) ÷ 1000 = 0.075 Ω Maximum = 0.075 + 0.1 = 0.175 Ω 75 m of 16 mm² R = (1.2 × 75) ÷ 1000 = 0.09 Ω Maximum = 0.09 + 0.1 = 0.19 Ω
Section 10 · Table 10.1 · p.71 · add 0.1 Ω Table 10.3 · extension lead lengths · p.75
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing