Disconnection times: Table 41.1Does every socket in a house need an RCD?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
411.3.2 sends you to Table 41.1, which gives the maximum disconnection times for final circuits. Its scope is 411.3.2.2 (p.71): final circuits not exceeding 63 A with one or more socket-outlets, and not exceeding 32 A supplying only fixed equipment. Read the column headings carefully — there are two halves and people pick the wrong one.
| System | 50 V < U₀ ≤ 120 V | 120 V < U₀ ≤ 230 V |
|---|---|---|
| TN (AC) | 0.8 s | 0.4 s |
| TT (AC) | 0.3 s | 0.2 s |
The table is for final circuits within 411.3.2.2. Distribution circuits, and final circuits outside 411.3.2.2, are handled by the regulations printed underneath the table:
| Circuit | TN | TT |
|---|---|---|
| Final, within 411.3.2.2 (230 V AC) | 0.4 s | 0.2 s |
| Distribution, or a final circuit over 63 A with sockets / over 32 A fixed equipment | 5 s | 1 s |
411.3.3 — socket outlets and additional protection
Sitting just below: 411.3.3, additional requirements for socket outlets and for mobile equipment used outdoors. Socket-outlets with a rated current not exceeding 32 A, and mobile equipment not exceeding 32 A used outdoors, require additional protection by a 30 mA RCD. It is not limited to homes: it covers sockets liable to be used by ordinary persons, sockets in other locations, and mobile equipment outdoors. The only exception is for sockets in other locations, and it needs a documented risk assessment by a skilled person. The regulation that is limited to domestic (household) premises is 411.3.4, for circuits supplying luminaires.
Table 41.1 · maximum disconnection times, final circuits 411.3.2.2 · p.71 · Table 41.1 scope: ≤ 63 A with sockets, ≤ 32 A fixed equipment 411.3.2.3 · p.72 · distribution circuits 5 s (TN) 411.3.2.4 · distribution circuits 1 s (TT) 411.3.3 · p.72 · socket outlets and outdoor mobile equipment ≤ 32 A, 30 mA additional protection
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing