The disconnection time decides which maximum earth fault loop impedance (Zs) table you use when designing. There are three tables, one after another:
| Table | Devices | Disconnection time | Page (A4) |
|---|---|---|---|
| 41.2 | Fuses: BS 88-2, BS 88-3, BS 3036, BS 1362 | 0.4 s | 74 |
| 41.3 | Circuit-breakers and RCBOs (their own table) | 0.4 s and 5 s | 75 |
| 41.4 | Fuses: BS 88-2, BS 88-3, BS 3036, BS 1362 | 5 s | 76 |
BS 7671 · Table 41.2 max Zs, fuses, 0.4 s · p.74 BS 7671 · Table 41.3 max Zs, circuit-breakers and RCBOs · p.75 BS 7671 · Table 41.4 max Zs, fuses, 5 s · p.76
- BS 88-2 / BS 88-3
- Cartridge style fuses (heavy-duty cartridge fuses)
- BS 3036
- Rewireable fuses (fuse wire). Still common in a lot of places.
- BS 1362
- Plug-top fuses (the fuse in a 13 A plug)
With a circuit-breaker or RCBO, it's simple: go straight to Table 41.3. You should still know the disconnection time and use it carefully in your design. It's with fuses that the disconnection time really matters, because it decides between Table 41.2 and 41.4. The top of each fuse table states the disconnection time it's for: 0.4 s on 41.2 and 5 s on 41.4.
A common way to put it is that circuit-breakers and RCBOs "have their own 0.4 disconnection time parameter". More exactly, the heading of Table 41.3 says its values give compliance with both the 0.4 s time (Table 41.1) and the 5 s time (Reg 411.3.2.3). That's why you don't need to pick between two tables for a breaker. Type D is the exception: Table 41.3 gives Type D separate 0.4 s and 5 s columns, so for a Type D the disconnection time still matters.
Example A · rewireable fuse, heating circuit
Circuit: BS 3036 rewireable fuse · final circuit · 20 A heating (fixed equipment) Final circuit, fixed equipment NOT above 32 A → Table 41.1 TN, AC, U₀ = 230 V → max disconnection time 0.4 s Fuse + 0.4 s → take max Zs from Table 41.2
Example B · rewireable fuse, feed to a shed
Circuit: BS 3036 rewireable fuse · feeds a consumer unit in a shed Feeds another board → distribution circuit → NOT Table 41.1 TN → Reg 411.3.2.3 → max disconnection time 5 s Fuse + 5 s → take max Zs from Table 41.4
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing