Devices and RCD typesType AC, A, F or B. Which RCD?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Chapter 53: devices for protection
Chapter 53 covers devices for protection, isolation, switching, control and monitoring. Know which job each device does — the exam tests exactly that distinction.
| Job | Device |
|---|---|
| Overcurrent protection | Circuit breaker, fuse, RCBO |
| Fault protection by ADS | The overcurrent device — or an RCD on a TT system |
| Additional protection | 30 mA RCD |
| Fire protection | RCD not exceeding 300 mA · AFDD |
| Monitoring | RCM — residual current monitor |
And a related one: the protective conductor current shall not contribute to the residual current measurement. An RCD compares line and neutral only.
Chapter 53 · protection, isolation, switching, control, monitoring 531 · devices for fault protection by ADS
RCDs: types, the 30 % rule and Table 41.5
Types of RCD
RCD types are marked on the device as pictograms, not letters — a plain sine wave for type AC, a sine wave plus a pulsating DC symbol for type A, and so on. Guidance Note 3 shows them in Figure 2.32 (p.97); BS 7671 (531.3.3, pp.165–166) describes Types AC, A, F and B in words only: a Type A still works with smooth DC up to 6 mA, a Type F up to 10 mA, and a Type B up to 0.4 × IΔn or 10 mA, whichever is higher. Type AC is effectively obsolete; type A is the normal choice now.
The 30 % earth leakage rule
Keep the normal standing leakage on one RCD below 30 % of its rated residual current, or you get nuisance tripping. An RCD may trip at any value above 50 % of its rating (531.3.2(c), p.165).
How much leakage a 30 mA RCD tolerates
30 % of 30 mA = 9 mA That is 9 mA across every circuit on that RCD, not 9 mA per circuit. For scale: a single computer can leak about 2 mA. Four computers (8 mA) and you're nearly there; five (10 mA) and you're over.
Table 41.5 and the 50 V touch voltage
On a TT system the RCD is doing fault protection, because the earth electrode gives a much higher resistance than a supplier's earth. Table 41.5 (p.77, under 411.5.4 in Chapter 41) gives the maximum earth fault loop impedance Zs for each RCD rating.
| IΔn | Max Zs | Check |
|---|---|---|
| 30 mA | 1667 Ω | 0.03 × 1667 = 50 V |
| 100 mA | 500 Ω | 0.1 × 500 = 50 V |
| 300 mA | 167 Ω | 0.3 × 167 = 50 V |
| 500 mA | 100 Ω | 0.5 × 100 = 50 V |
Table 41.5 · p.77 · maximum Zs per RCD rating 531.3.2(c) · p.165 · standing leakage ≤ 30 % of IΔn · may trip above 50 % 531.3.3 · pp.165–166 · RCD types AC, A, F and B in words Guidance Note 3 · Figure 2.32 · p.97 · RCD type pictograms
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing