Chapter 53 covers devices for protection, isolation, switching, control and monitoring. Know which job each device does — the exam tests exactly that distinction.

JobDevice
Overcurrent protectionCircuit breaker, fuse, RCBO
Fault protection by ADSThe overcurrent device — or an RCD on a TT system
Additional protection30 mA RCD
Fire protectionRCD not exceeding 300 mA · AFDD
MonitoringRCM — residual current monitor
§531 — an RCD shall disconnect all live conductors of the circuit. Look at the top of any RCD: line and neutral both land on it, and both are broken.

And a related one: the protective conductor current shall not contribute to the residual current measurement. An RCD compares line and neutral only.

Chapter 53 · protection, isolation, switching, control, monitoring 531 · devices for fault protection by ADS

RCDs: types, the 30 % rule and Table 41.5

Types of RCD

✋Don't confuse RCD types with breaker types. Circuit breakers have only B, C and D. RCDs have AC, A, F and B — and an S type, which is time-delayed.

RCD types are marked on the device as pictograms, not letters — a plain sine wave for type AC, a sine wave plus a pulsating DC symbol for type A, and so on. Guidance Note 3 shows them in Figure 2.32 (p.97); BS 7671 (531.3.3, pp.165–166) describes Types AC, A, F and B in words only: a Type A still works with smooth DC up to 6 mA, a Type F up to 10 mA, and a Type B up to 0.4 × IΔn or 10 mA, whichever is higher. Type AC is effectively obsolete; type A is the normal choice now.

The 30 % earth leakage rule

Keep the normal standing leakage on one RCD below 30 % of its rated residual current, or you get nuisance tripping. An RCD may trip at any value above 50 % of its rating (531.3.2(c), p.165).

How much leakage a 30 mA RCD tolerates

30 % of 30 mA = 9 mA

That is 9 mA across every circuit on that RCD,
not 9 mA per circuit.

For scale: a single computer can leak about 2 mA.
Four computers (8 mA) and you're nearly there;
five (10 mA) and you're over.
This is why a board with ten circuits on one RCD is asking for nuisance tripping, and why splitting circuits across two RCDs — or using RCBOs — is better design.

Table 41.5 and the 50 V touch voltage

On a TT system the RCD is doing fault protection, because the earth electrode gives a much higher resistance than a supplier's earth. Table 41.5 (p.77, under 411.5.4 in Chapter 41) gives the maximum earth fault loop impedance Zs for each RCD rating.

IΔnMax ZsCheck
30 mA1667 Ω0.03 × 1667 = 50 V
100 mA500 Ω0.1 × 500 = 50 V
300 mA167 Ω0.3 × 167 = 50 V
500 mA100 Ω0.5 × 100 = 50 V
=Every row is the same sum: Zs × IΔn = 50 V. The whole table exists to keep touch voltage at or below 50 V. Ohm's law, nothing more.
The Δ symbol. IΔn is the rated residual operating current — the triangle is delta, meaning difference. Its definition is in Part 2.

Table 41.5 · p.77 · maximum Zs per RCD rating 531.3.2(c) · p.165 · standing leakage ≤ 30 % of IΔn · may trip above 50 % 531.3.3 · pp.165–166 · RCD types AC, A, F and B in words Guidance Note 3 · Figure 2.32 · p.97 · RCD type pictograms

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.