External influences: 522 and Appendix 5

Section 522 is the selection of wiring systems for the external influences they'll face. It gives the codes and examples; Appendix 5 gives the detail.

CodeInfluenceNotes
AAAmbient temperatureLeads to the Ca factor
AEPresence of solid foreign bodiesExpressed as IP ratings — dust, fingers, tools
AGImpact / mechanical stressAG1 low (household) · AG2 medium (industrial)
AHVibration
AKPresence of flora / mould
BACapability of personsBA1 ordinary · BA2 children · BA4 instructed · BA5 skilled
↔Which book, which question. Asked what a code means (what is AG2?) → Appendix 5. Asked what influences you must consider for a wiring system → 522. The two interlock, and that's deliberate.

The AE row is a neat example of the book joining up: "presence of solid foreign bodies" is expressed as IP ratings — the same IP2X and IP4X from Section 416 earlier, arriving from a completely different direction.

522 · selection for external influences Appendix 5 · classification codes in detail

Current-carrying capacity and Appendix 4

Section 523 covers current-carrying capacity, and sends you to Appendix 4 for the numbers.

CableMax operating temperature
Thermoplastic (PVC) — standard grey twin & earth70 °C
Thermosetting90 °C

523 also explains why the neutral counts as a live conductor: it carries current in normal service, so it has to be allowed for. Harmonics are the case where the neutral current can exceed the line current.

Finding your way round Appendix 4

≡Tables ending in A = current-carrying capacity. Tables ending in B = voltage drop. The exception is Table 4D5 — flat twin & earth — which gives both in one table.

Also check whether you're on copper or aluminium conductors, and match the installation reference method.

10 mm² twin & earth, copper, reference method C

Appendix 4 → Table 4D5
"70 °C thermoplastic sheathed and insulated
 flat cable with protective conductor" = twin & earth

10 mm² row, reference method C column
It = 64 A

Volt drop, from the same appendix:

Volt drop = (mV/A/m × Ib × L) ÷ 1000
Correction factors live here too. For a cable up to 10 mm² surrounded by thermal insulation, Appendix 4 section 2.6 (p.451) gives Ci by length: 50 mm 0.88, 100 mm 0.78, 200 mm 0.63, 400 mm 0.51, and 0.5 for 0.5 m or more — in the notes ahead of the tables, not in the tables themselves. Anything to do with cable rating factors, current capacity or volt drop is Appendix 4.

523 · current-carrying capacity Table 52.2 · maximum operating temperatures Appendix 4 · It values, volt drop, correction factors Table 4D5 · flat twin & earth

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside