Correction factors (Ca, Cg and more)Why does a cable in a hot loft carry less current?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

A simple shower example has no correction factors. In real installations, the environment around a cable can reduce how much current it can safely carry, so we correct for it and usually end up with a bigger cable.

It ≥ In ÷ (Ca × Cg × Ci × Cc × Cf …)
Only multiply in the factors that apply to the question, then pick a cable whose tabulated rating It is at least that figure. Its capacity as installed is Iz = It × Ca × Cg × …, which is then at least In.
FactorWhat it corrects forWhere to find it
CaAmbient temperature around the cable (not the room). Tables are based on 30 °C air, where the factor is 1. Buried cables use a 20 °C ground temperature instead.OSG Table F1 · BS 7671 Table 4B1
CgGrouping: several circuits run bunched together along the same routeOSG Table F3 · BS 7671 Table 4C1
CiThermal insulation around the cableOSG · BS 7671
CcCable buried in the ground (in a duct or direct): factor 0.9BS 7671 only
CfCircuit protected by a BS 3036 rewireable fuse: factor 0.725BS 7671 only

In exam questions you'll be given the temperature and the number of grouped circuits. You don't measure them. In the exam you mainly need Ca, Cg and Ci.

On-Site Guide · Appendix F · Table F1 ambient temperature factors (Ca) · p.184 On-Site Guide · Table F3 grouping factors (Cg) · p.186 On-Site Guide · It ≥ In ÷ factors formula and some factors · p.183

BS 7671 · Appendix 4 · list of symbols Ca, Cg, Ci, Cc, Cf (incl. Cf 0.725 and Cc 0.9) · p.452 Highlight Cf and Cc

BS 7671 · Table 4B1 ambient temperature factors · p.469 BS 7671 · Table 4C1 grouping factors · p.471

Reading Table 4C1
Choose the arrangement row. The shower cable isn't on a ladder, a tray, or a single layer on a wall or floor, so it's "bunched in air, on a surface, embedded or enclosed". Then read across to the number of circuits. "Grouped with two other circuits" means 3 circuits in total.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside