Continuity when you can't isolateThe circuit can't be switched off. How do you test the cpc?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
Q16Book · a hidden periodic question

A server room circuit feeds metal-clad accessories and can't be switched off. How do you check cpc continuity?

  1. aWith an earth fault loop impedance tester
  2. bWith a voltage indicator, line to earth
  3. cWith a long (wandering) lead and a low-resistance ohmmeter
  4. dWith a polarity indicator between neutral and earth

Answer c. "Can't be switched off" tells you it's a periodic, even though it doesn't say so. On initial verification the circuit would be dead anyway.

  • Normally you'd use test method 1 (R1 + R2): link line and cpc at the board, then test between the line and cpc terminals at every point, e.g. every luminaire and every switch on a lighting circuit. That needs the circuit dead.
  • Section 3.10 covers testing during periodics. It's short and refers back to the section 2 tests (2.6.5 onwards), but it adds some extra points.
  • Where you can't isolate, don't disconnect protective and bonding conductors. Under fault conditions, exposed and extraneous-conductive-parts could rise to a dangerous voltage.
  • The next paragraph gives the convenient way: the wandering lead (long lead) method. Clip the long lead to the MET, then touch the other lead on each metal accessory: switch screw heads, metal-clad sockets and luminaire casings. Be careful up steps, and cordon off the area.
MET low-resistance ohmmeter clip long (wandering) lead metal-clad socket metal switch plate luminaire casing then visit every point in turn Circuit stays live · earthing and bonding conductors stay connected
The wandering (long) lead method measures from the MET to each metal accessory, so you don't have to switch the circuit off.

GN3 · 2.6.5 continuity, test method 1 (R1 + R2) GN3 · 3.10 testing during periodic inspection GN3 · can't isolate: don't disconnect protective conductors, use the wandering / long lead · 3.10.3 · p.128

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside