A low-resistance ohmmeter throughout. The order catches people out:
| Order | What | Test |
|---|---|---|
| 1st | Main protective bonding | R2 — end to end |
| 2nd | Lighting and radial circuits | R1+R2 |
| 3rd | Ring final circuits | Three steps — below |
✋Not the earthing conductor. The obvious answer is to start at the earthing conductor — but proving that is part of Ze, which is a live test and comes much later. Main protective bonding is a dead test and goes first.
R2 is not only for the green-and-yellow. It is an end-to-end test on any single conductor, proving there is no break in it. Step 1 of the ring test is three R2 tests — on line, on neutral, on CPC.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing