Continuity method 2 on a CPCYou switch the light off mid-test. What changes?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep
  1. Isolate. Disconnect the circuit’s CPC from the earth bar, so you’re measuring that CPC alone, with no parallel paths.
  2. Clip the long lead onto the disconnected CPC. Tight — a loose crocodile clip gives a high, wandering reading.
  3. With your other lead, go to every point and probe the CPC terminal. Record the highest reading.
Board CPC off the earth bar R₂ · the CPC alone each point: CPC terminal long (wandering) lead · nulled ohmmeter
One conductor, end to end. Operate a light switch during the test and nothing changes — method 2 never touches the line, so it proves nothing about switching or polarity.
A socket on the circuit? The plug-in adapter is no use here — it puts all your probe points in the socket, and method 2 needs one end at the board. Probe the socket’s earth contact directly instead.

Record it in the R2 column (column 22) of the schedule of test results, and N/A the R1 + R2 column (21). (Using method 1? The other way round.) Put the CPC back on the earth bar when you’re done.

✋For circuits, method 1 is still better.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside