Continuity of protective conductors, including main and supplementary bonding, can be tested two ways. Do them in either order; in the assessment both count as the first test in the sequence.

Test method 1 needs a line conductor: you link line and CPC at the board and test across them at each point. Bonding has no line conductor. So for the bonding there is only one method: test method 2.

Method 1 · R₁ + R₂ ✓ proves the CPC ✓ largely proves polarity ✓ proves the switches ✗ needs a line conductor the one to reach for on circuits Method 2 · R₂ ✓ proves the CPC ✓ proves bonding — the only way ✗ not polarity ✗ not the switches the long lead · one conductor, end to end
Method 1 for circuits, wherever you can. Method 2 for bonding, always, and for CPCs when method 1 isn’t possible.

Guidance Note 3 · 2.6.5 · test methods 1 and 2

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside