Continuity: method 1 or method 2?Why can't you test bonding with R1 plus R2?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Continuity of protective conductors, including main and supplementary bonding, can be tested two ways. Do them in either order; in the assessment both count as the first test in the sequence.
Test method 1 needs a line conductor: you link line and CPC at the board and test across them at each point. Bonding has no line conductor. So for the bonding there is only one method: test method 2.
Guidance Note 3 · 2.6.5 · test methods 1 and 2