Cold cable, and correcting for ambient temperatureSame cable, 40 degrees. What changes?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

What "cold cable" means

Every calculation so far has been for a cold cable. Imagine the cable still on the drum, or installed but not yet energised and commissioned.

Table B1 figures are a cold cable at 20 °C

That is the state the installation is in when you turn up to do the dead tests — wired, but never switched on. Once it is in service and carrying load, the cable warms up and the resistance rises.

Correcting for ambient temperature

Guidance Note 3 · Appendix B · Table B2 · p.175, "Ambient temperature multipliers (α) to Table B1". Table B1 is at 20 °C. If the ambient temperature on the test day is different, the calculation gains one more term:

R = (mΩ/m × length × Table B2 multiplier) ÷ 1000

The Table B2 multiplier corrects the 20 °C figure to the ambient temperature you are testing in. At 20 °C the multiplier is 1, so there is nothing to apply — you only reach for it above or below 20 °C.

The same 4/1.5 cable, 10 m, but tested at 40 °C ambient

mΩ/m for 4/1.5 = 16.71
Length            = 10 m
Table B2 at 40 °C = 1.08

R = (16.71 × 10 × 1.08) ÷ 1000
  = 180.5 ÷ 1000
  = 0.1805
  = 0.18 Ω   (against 0.17 Ω at 20 °C)
You can apply it either way round. Put the multiplier into the formula, or take the 20 °C answer you already have and multiply it by 1.08. Same result.
Higher temperature, higher resistance

Resistance rises with temperature — but not in proportion, the way it does with length. Going from 20 °C to 40 °C adds about 8% (the 1.08); it does not double it. At 15 °C ambient the resistance would come out lower than the 20 °C figure.

✋It is a test multiplier, not Ca. Table B2 corrects a conductor resistance from 20 °C for testing. Ca is a different thing: the ambient temperature rating factor used when sizing a cable's current-carrying capacity. Cf, the factor for a semi-enclosed fuse, is 0.725.
Where the multipliers live. Guidance Note 3 · Appendix B · Table B2 · p.175, alongside Table B1. The Ca rating factors in BS 7671 · Appendix 4 and On-Site Guide · Table F1 are for cable design, not for correcting a test reading.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside