Circuit breakers, torque and the DIN railDoes a breaker protect against earth faults?

Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.

From Sparky’s full video lesson. Members get the whole lesson on every notes page.

The notes

Exactly as they are on the site.

Download these notesPDF · free to keep

Our example breaker is marked B32 and BS EN 60898: a Type B, 32 A circuit breaker.

  • Types B, C and D differ in how much inrush (starting) current they'll allow before tripping. Circuits need more current to get going than to keep going.
  • Type B: most domestic circuits, which have very little start-up current.
  • Type C: commercial and industrial, e.g. motor circuits with a high starting current that settles to a running current.
  • Type D: circuits with a really high starting current.
  • They all look the same apart from the letter, and fit the same board.

BS EN 60898 · circuit breakers (Types B, C, D) B up to 5 × In, C 10 × In, D 20 × In

Fitting the breaker and torque

  • The breaker hooks over the DIN rail at the top and drops onto the busbar "spine". The terminal screw closes a gap that clamps onto the busbar or conductor, rather than screwing into a thread.
  • Terminal screws must be tightened to the manufacturer's torque setting, in newton metres (N m). Our breaker is marked 2.3 N m on its side.
  • Use a torque screwdriver set to 2.3. When you reach the setting it "breaks" (clicks and slips) so you can't overtighten. Torque settings became a big focus from the start of the 18th Edition (2018). It's part of following the manufacturer's instructions.
  • Loose-looking breakers on a half-empty board aren't loose connections. They sit firm once the board is filled and the cover is on.
Commonly misheard
It sounds like "bin rail". It's the DIN rail, the standard metal mounting rail the devices clip onto.
Do CBs protect against earth faults?
It's often said a circuit breaker protects against short circuits, earth faults and overloads, but doesn't give brilliant earth-fault protection, especially the sensitive additional protection a 30 mA RCD gives. A CB will clear an earth fault if the fault current is high enough (low enough Zs), but it can't detect small leakage currents like an RCD can.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside