Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Guidance Note 3 · pp.83–84. The formula that decides it:
RA × I∆n ≤ 50 V
RA = 82 Ω, trying a 300 mA device
Put the milliamps into amps first: 300 mA = 0.3 A 82 × 0.3 = 24.6 V ≤ 50 V, so it satisfies the requirement
And a 30 mA device, for comparison
82 × 0.03 = 2.46 V also well inside 50 V
So both pass the formula. The choice between them comes from what else the circuit needs:
✋Both satisfy RA × IΔn ≤ 50 V. A 30 mA device goes wherever additional protection is required. A 300 mA device upstream is chosen for selectivity with the 30 mA devices below it, and to avoid nuisance tripping. And a TT electrode reading can drift upward — 82 Ω today could be 150 Ω in a dry spell.
Check the headroom too. If a circuit's R1 + R2 takes Zs to 82.5 Ω, ask whether that still leaves room for the ground to dry out. Choosing the device is a judgement, not just a calculation that passes.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing