Chapter 54 covers earthing arrangements and protective conductors. If a question mentions main protective bonding or supplementary bonding, you're going to 544. If it's about the earthing arrangement itself, you're earlier in the chapter.

The earthing systems — including the two you won't install

SystemNotes
TTThe one that needs an earth electrode
TN-SSeparate earth throughout — the old lead-sheathed supply
TN-C-SCombined then separated. PME is a version of TN-C-S
ITHigh-impedance system. You are unlikely to meet one
TN-CTerra Neutral Combined — earth and neutral combined all the way in and never separated. Not permitted in UK consumer installations (ESQCR Reg 8(4): no PEN conductor in a consumer's installation). You may meet it working abroad
Why TN-C is worth five seconds of your time. The question "which combination of those letters haven't we used?" is exactly how an exam writer builds a distractor. Knowing TN-C exists, and that it's not allowed here, stops you second-guessing the three that are.

Table 54.1 — a buried earthing conductor

This table gives the minimum cross-sectional area of an earthing conductor that is buried in the ground, and it splits on two questions: is it protected against mechanical damage, and is it protected against corrosion by a sheath?

ConditionMinimum CSA
Protected against mechanical damage and against corrosion by a sheath
e.g. buried inside conduit or ducting
2.5 mm² copper · 10 mm² steel
Not protected against mechanical damage, but protected against corrosion by a sheath16 mm² copper · 16 mm² coated steel
Not protected against corrosion — mechanical protection irrelevant25 mm² copper · 50 mm² steel
Highlight the last row in Table 54.1 (p.208). With no protection against corrosion, a buried earthing conductor must be at least 25 mm² copper or 50 mm² steel, whatever its mechanical protection.

542.4 — the main earthing terminal

Part 1's fundamental principles said every installation must have an earthing arrangement. Part of that arrangement is a main earthing terminal (MET) or earth bar, and every installation must have one, because five different things have to land on it:

  1. The earthing conductor
  2. Circuit protective conductors
  3. Main protective bonding conductors
  4. Functional earthing conductors, where required
  5. Lightning protection system bonding, where there is one
≡The earthing terminal may be external or internal. You need one or the other, not both — as long as it lets you get the earthing conductor from the supplier's head through to your final circuits.

Chapter 54 · earthing arrangements and protective conductors Table 54.1 · p.208 · minimum CSA of a buried earthing conductor ★ 542.4 · main earthing terminal · what connects to it ★ 544 · protective bonding conductors

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside