Chapter 54: earthing arrangements and the METTN-S, TN-C-S, TT. Which can you install?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
Chapter 54 covers earthing arrangements and protective conductors. If a question mentions main protective bonding or supplementary bonding, you're going to 544. If it's about the earthing arrangement itself, you're earlier in the chapter.
The earthing systems — including the two you won't install
| System | Notes |
|---|---|
| TT | The one that needs an earth electrode |
| TN-S | Separate earth throughout — the old lead-sheathed supply |
| TN-C-S | Combined then separated. PME is a version of TN-C-S |
| IT | High-impedance system. You are unlikely to meet one |
| TN-C | Terra Neutral Combined — earth and neutral combined all the way in and never separated. Not permitted in UK consumer installations (ESQCR Reg 8(4): no PEN conductor in a consumer's installation). You may meet it working abroad |
Table 54.1 — a buried earthing conductor
This table gives the minimum cross-sectional area of an earthing conductor that is buried in the ground, and it splits on two questions: is it protected against mechanical damage, and is it protected against corrosion by a sheath?
| Condition | Minimum CSA |
|---|---|
| Protected against mechanical damage and against corrosion by a sheath e.g. buried inside conduit or ducting | 2.5 mm² copper · 10 mm² steel |
| Not protected against mechanical damage, but protected against corrosion by a sheath | 16 mm² copper · 16 mm² coated steel |
| Not protected against corrosion — mechanical protection irrelevant | 25 mm² copper · 50 mm² steel |
542.4 — the main earthing terminal
Part 1's fundamental principles said every installation must have an earthing arrangement. Part of that arrangement is a main earthing terminal (MET) or earth bar, and every installation must have one, because five different things have to land on it:
- The earthing conductor
- Circuit protective conductors
- Main protective bonding conductors
- Functional earthing conductors, where required
- Lightning protection system bonding, where there is one
Chapter 54 · earthing arrangements and protective conductors Table 54.1 · p.208 · minimum CSA of a buried earthing conductor ★ 542.4 · main earthing terminal · what connects to it ★ 544 · protective bonding conductors
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing