Chapter 52: wiring systems

First, what the book means by the term. Look it up in Part 2:

?A wiring system is an assembly of cables or busbars together with the parts that secure and, if necessary, enclose them.

So conduit, trunking, cable tray, ducting, busbar and power track are all wiring systems. A consumer unit is an enclosure, but it isn't a wiring system.

Table 4A1 — what you may install, and how

In Appendix 4, Table 4A1 lists cable types against installation methods and tells you which are permitted.

CableClipped directConduit / trunkingOn insulators
Bare conductor✗✗✓
Non-sheathed (single core)✗✓✓
Multicore (e.g. twin & earth)✓✓✓
✋The classic confusion. Twin & earth contains a bare CPC, so people conclude they're clipping a "bare conductor", which the table forbids. They aren't. That CPC is part of a sheathed multicore cable, and the multicore row is the one that applies. The bare-conductor row means a genuinely bare conductor on its own — overhead lines on insulators.

The same chapter gives you the installation reference methods you met in cable design: A, B, C and the numbered ones 100 to 103.

Part 2 · definition of a wiring system 521.4 · types of wiring system Table 4A1 · permitted installation methods Table 4A2 · installation reference methods

Premature collapse in the event of a fire

One of the most quoted regulations in recent editions, and it has a reason behind it.

§521.10.202 — wiring systems shall be supported so that they are not liable to premature collapse in the event of a fire.
Why it exists. In a fire, cables held only by plastic clips can come down when the plastic melts.

So plastic clips alone are not a suitable method. The cables need support that will not give way early in a fire.

WhereWhat you'll find
BS 7671 · 521.10.202The requirement: support against premature collapse in a fire (cited in Guidance Note 3, p.47)
On-Site Guide · Appendix DActual spacing tables, by cable diameter, horizontal and vertical — in millimetres
A rule of thumb from the trade: clip spacing about elbow-to-wrist, or the width of your hammer. Fine on site, but the table is what's assessed.

521.10.202 · premature collapse in the event of a fire · cited in GN3 p.47 On-Site Guide · Appendix D · cable support spacings

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside