Chapter 42 is protection against thermal effects — fire, burns, harmful heat, thermal radiation, degradation of materials, propagation of flame and smoke.

SectionCovers
421Protection against fire caused by electrical equipment
422Locations where particular risks of fire exist — stored or processed materials

421.1.201 — the non-combustible consumer unit

§In domestic (household) premises, consumer units and similar switchgear assemblies shall have their enclosure manufactured from non-combustible material, or be enclosed in a cabinet or enclosure constructed of non-combustible material. The note gives the example: a ferrous metal, such as steel.

So a plastic consumer unit only qualifies inside a non-combustible cabinet or enclosure. It's a fair bet for a question. Notice too that 421 refers you back to Section 132 in Part 1 — another reminder that the book constantly cross-references itself.

421.1.7 — arc fault detection devices

AFDDs are no longer merely recommended. The regulation says they shall be provided, to BS EN 62606, for single-phase AC final circuits supplying socket-outlets not exceeding 32 A in four kinds of premises: higher-risk residential buildings (residential buildings over 18 m in height or in excess of six storeys, whichever is met first), houses in multiple occupation, purpose-built student accommodation and care homes. Everywhere else they are recommended for the same circuits. Where one is used, it goes at the origin of the circuit it protects.

The Grenfell Tower inquiry findings fed into this regulation. It wasn't the sole reason for it, but the inquiry's conclusions were incorporated — which is why the wording moved from "recommended" to "shall" for those building types.

422 — locations with a fire risk

Where there's a fire risk due to the nature of processed or stored materials, measures shall be taken to limit equipment surface temperature. The figure to know:

90 °C
Maximum enclosure temperature under normal conditions (a heater, for example) in such a location

Chapter 42 · protection against thermal effects 421.1.201 · non-combustible consumer unit enclosure 421.1.7 · p.93 · AFDDs, socket outlet final circuits ≤ 32 A 422 · fire risk locations · 90 °C under normal conditions

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside