Chapter 41 and automatic disconnection

Part 4 is where the exam weight is, and Chapter 41 is the biggest chapter in it — big enough to have its own contents page. Open Part 4 and you get an intro, a scope, then Chapter 41: protection against electric shock.

§Section 410 — protective measures shall consist of independent provision.

The main sections of Chapter 41, in book order:

SectionCovers
411Automatic disconnection of supply (ADS) — the big one
412Double or reinforced insulation
413Electrical separation
414Extra-low voltage (SELV and PELV)
416Provisions for basic protection

Inside 411 sits the regulation this whole part revolves around:

§411.3.2 — automatic disconnection in case of a fault. A protective device shall automatically interrupt the supply to the line conductor of a circuit or equipment in the event of a fault.
✋That's the device providing automatic disconnection for that circuit. Normally it is the circuit's overcurrent protective device (a circuit breaker, a fuse or an RCBO), or an RCD where it gives the fault protection, as on a TT system.

Chapter 41 · protection against electric shock (own contents page) Section 410 · independent provision 411.3.2 · automatic disconnection in case of fault

Final circuits vs distribution circuits

Before the tables make sense you need this distinction, because the whole of Table 41.1 hangs on it — and it's not about rings versus radials.

Main board Sub board Socket distribution circuit board to board · 5 s (TN) final circuit board to outlet · 0.4 s (TN) supply
The cable between two boards is a distribution circuit. The cable from a board to the thing the user plugs into is a final circuit. Every circuit you install is one or the other.
FFinal circuit
Consumer unit → outlet. The circuits the person you hand the installation to actually uses. Sockets, lights, cooker, shower.
DDistribution circuit
Board to board. Main board to a garage sub-board; the supply from the transformer into the main board.
Quick identification in an exam question. 0.4 s → a final circuit within 411.3.2.2 (≤ 63 A with sockets, ≤ 32 A fixed equipment). 5 s → a distribution circuit, or a final circuit over 63 A with sockets or over 32 A fixed equipment (411.3.2.3).

Part 2 · definitions of final circuit and distribution circuit

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.