Cable selection: the 7 stepsFrom the load to the cable size. Seven steps. Know them?
Free from the notes: Sparky’s video on it, the section word for word as members see it, and a PDF to keep.
The notes
Exactly as they are on the site.
- Work out the design current, Ib. Ib = P ÷ V. Also note the installation reference method now, from the question.
- Select the protective device rating, In (e.g. B40), so that In ≥ Ib.
- Identify the installation method (C, B, A, 100–103…).
- Apply any correction factors, e.g. ambient temperature, grouping or thermal insulation.
- Calculate the tabulated current, It, that the cable must be able to carry.
- Select the cable size from the tables (BS 7671 or the On-Site Guide).
- Check the voltage drop.
- Ib
- Design current of the circuit: the load. "Ib", not "ID".
- In
- Nominal rating of the protective device in amps, e.g. the "6" on a B6.
- Iz
- Current-carrying capacity of the cable under normal conditions once correction factors have been applied. The Z here has nothing to do with impedance.
- It
- Tabulated current-carrying capacity: the value straight from the tables.
With no correction factors, Iz = It, so you pick a cable whose tabulated rating It ≥ In.
Voltage drop: radial circuits
VD = (mV/A/m × Ib × L) ÷ 1000 ÷1000 because mV/A/m is in millivolts
Voltage drop: ring final circuits
VD = (mV/A/m × Ib × L) ÷ 4000 ÷4000: the ring is two legs in parallel, each about half the length to the load, so the drop is ½ × ½ = ¼ of a radial (mV/A/m already covers line + neutral)
| Max voltage drop | Single-phase 230 V | Three-phase 400 V |
|---|---|---|
| Lighting: 3% | 6.9 V | 12 V |
| All other circuits (sockets, showers, cookers): 5% | 11.5 V | 20 V |
The 3% and 5% are measured from the origin of the installation, not from the consumer unit a circuit happens to start at. If the voltage drop is too high, upsize the cable. You never downsize.
On-Site Guide · Appendix F: voltage drop explanation, radial formula and ring formula · p.184 Highlight the formula and the 3% / 5% paragraph
On most jobs a designer, your boss or the company has already done these calculations, and you install to the design. You still need to know the method for the exam. Higher-level design qualifications take it much further.
Free section from Sparky Study Notes. The full Level 3 notes, 1,463 practice questions and the video lessons: sparkystudynotes.co.uk
Test yourself on it
The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.
Get new notes and exam tips from Sparky
About one email a fortnight. Unsubscribe any time. Privacy noticeThat was one section. There are 583.
Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.
- 583sections of written notes
- 35video lessons
- 1,463practice questions
- 146diagrams, redrawn
- 18th Edition
- Building Regs
- PAT
- Fundamental Inspection & Testing
- Initial Verification
- Periodic Inspection & Testing