We work through one design scenario from start to finish. Page numbers are given as we go so you can follow in your own books. The books used are BS 7671, the On-Site Guide, Guidance Note 3 and the Electrician's Guide to the Building Regulations. The idea is to pull together regulations that turn up in different modules and show how they all feed into one circuit.

The design brief

A circuit supplying a 9.6 kW cooker is to be installed. You are the designer.
Design the circuit according to regulations and guidance.

· Existing installation has adequate earthing and bonding
· Earthing arrangement TN-C-S, measured Ze = 0.26 Ω
· Circuit length 27 m
· Run in PVC trunking with 2 other circuits, then vertically down
  the wall in a chase at a depth of 30 mm to the cooker control
  switch and the cooker outlet
· Ambient temperature 35 °C
· Client wants a socket-outlet on the cooker control switch
· Consumer unit: non-combustible dual RCD board, Type 2 SPD,
  spare ways on both the "protected" and "non-protected" side
· Cooker is in the shared kitchen of a house in multiple
  occupation (HMO)
CU 32 A Type B RCBO + AFDD 30 mA PVC trunking, grouped with 2 other circuits Reference Method B Cooker 9.6 kW Cooker control unit 45 A DP switch + socket-outlet Cooker outlet ("cooker nose"), deep box chase, 30 mm deep, thermally insulating wall (assumed) Ref Method A Circuit length 27 m Ambient 35 °C TN-C-S · Ze 0.26 Ω HMO shared kitchen
Our scenario. The cable passes through two installation methods. You design to the worst one.

Make your own versions. These are the parts you can change to get a fresh question every time: the load (a 3 kW heater, a 10 kW shower…), the Ze, the circuit length, the grouping, the ambient temperature and the cable type. Using the books for their real purpose is the best way to learn your way round them. They're industry books written by the IET, not textbooks.

Exam reality
A full design like this won't come up in your multiple-choice exams. That's Level 4 (design and verification) territory, where there are written questions this deep. But the pieces will come up: finding a correction factor for an ambient temperature, finding the mV/A/m for voltage drop, and so on. Being able to do the whole thing also makes you a much better electrician.

Talk to the client. You can't design well without knowing where things go (that sets the circuit length) and how the client will use the circuit. Sometimes you'll have to tell them a position isn't allowed because of a regulation.

Test yourself on it

The tests are in the members’ area. Get one wrong and it shows you why, and where to revise.

Get access

Get new notes and exam tips from Sparky

About one email a fortnight. Unsubscribe any time. Privacy notice

That was one section. There are 583.

Sparky Study Notes is the whole Level 3 syllabus written up like this: the explanation, the worked example, and where it is in your book. With a video lesson for every part and a practice paper for every exam.

  • 583sections of written notes
  • 35video lessons
  • 1,463practice questions
  • 146diagrams, redrawn
  • 18th Edition
  • Building Regs
  • PAT
  • Fundamental Inspection & Testing
  • Initial Verification
  • Periodic Inspection & Testing
Get access — £100 12 months. One payment. See what’s inside